SC SOURCING BRIEFHONEYWELL · Experion Series C I/O / Digital Output

CC-PDOB01

Series C 24 V DC Digital Output Module

Series C 24 V DC Digital Output Module for switching 24 v dc field loads from series c i/o, supplied against the exact Honeywell part number with system and revision compatibility checked before quotation.

BRANDHoneywell
STOCK CONFIRMATIONLead time: 2–3 days
CONDITIONBrand new and original
WARRANTY12 months

Product overview

The Honeywell CC-PDOB01 is a 32-channel, field-isolated, bussed 24 V DC digital-output IOM for Series C. It switches solenoid valves, interposing relays and other process loads, and supports internal or external field excitation. All bussed outputs share a common return.

Built-in diagnostics, fuse-less short-circuit protection and per-channel operating modes reduce external components and simplify fault finding. Each channel can be configured for latched, pulsed or pulse-width-modulated output, with direct/reverse operation and FAILOPT safe-state behavior.

For the standard arrangement use CC-TDOB01 as the 9-inch non-redundant IOTA or CC-TDOB11 as the 12-inch redundant IOTA. Relay-output IOTAs CC-TDOR01, CC-TDOR11 and CC-SDOR01 are separate application options and must be selected against contact type, load and architecture.

COMMON APPLICATIONS

Installed-system context

  • Solenoid and relay outputs
  • 24 V DC process interlocks
  • Series C digital output

Tell us the controller, communication network and installed panel details. That context helps prevent a visually similar but incompatible replacement.

Manufacturer
Honeywell
Part number / MPN
CC-PDOB01
Product designation
Series C 24 V DC Digital Output Module
I/O type
Digital output module
Signal class
24 V DC discrete outputs
Platform
Experion Series C I/O
Termination
Use with compatible output IOTA
Load
Confirm current, inrush and protection
I/O model
CC-PDOB01 — 24 V digital output, field isolated, bussed output
Output channels
32
Output type
Source output; common-return bussed arrangement
Field / load voltage
15–30 V DC maximum operating range
Current per channel
0.5 A maximum
Module current capacity
Up to 6 A per module; group capacity depends on short-circuit condition
Eight-channel group limit, no short
4 A per group
Eight-channel group limit, one short
3 A per group
Eight-channel group limit, two shorts
1.5 A per group
Isolation
1500 VAC RMS or ±1500 V DC galvanic isolation
Off-state leakage
5 µA maximum
Turn-on / turn-off time
10 ms maximum
Redundancy switchover output gap
0 ms
Output voltage drop
Source voltage minus 150 mV maximum
Output modes
Latched, pulsed or pulse-width modulated per channel
Safe-state behavior
FAILOPT per channel: hold last value or shed to a configured safe value
Short-circuit protection
Fuse-less; faulted channel is de-energized until the short is repaired
Standard IOTAs
CC-TDOB01 non-redundant 9 in; CC-TDOB11 redundant 12 in
Relay IOTA options
CC-TDOR01 / CC-TDOR11 with CC-SDOR01 extension where the approved relay-output design requires them

Technical values are compiled from official Honeywell product documentation for this exact article number. Always check the delivered unit nameplate and revision before installation.

What to send for verification

  • • Complete Honeywell part number and clear nameplate photo
  • • load voltage, steady current and inrush current
  • • CC-TDOB01 / CC-TDOB11 or approved relay-IOTA arrangement
  • • internal versus external field excitation
  • • common-return wiring, redundancy and FAILOPT safe-state configuration
  • • Experion release, hardware revision and required approvals
  • • Required quantity, destination and condition

What your quotation will state

  • • Exact quoted article number
  • • New, surplus or refurbished condition
  • • Available quantity and estimated lead time
  • • Warranty and proposed shipping method

Confirm voltage, load, IOTA, fusing, wiring and release.

BUYER QUESTIONS

Frequently asked questions

How many outputs does CC-PDOB01 provide?

It provides 32 source-type 24 V DC digital-output channels in a field-isolated, bussed common-return arrangement.

Which IOTA is used with CC-PDOB01?

The standard digital-output IOTAs are CC-TDOB01 for non-redundant 9-inch installations and CC-TDOB11 for redundant 12-inch installations. Approved relay-IOTA arrangements use different termination assemblies and must be checked separately.

Does the module require replaceable output fuses?

The datasheet describes fuse-less short-circuit protection. Internal circuitry detects a short and removes power from the affected field connection until the fault is repaired.

What happens to outputs during a control or communication fault?

FAILOPT is configured per channel. The output can hold its last value or shed to a user-configured safe value, depending on the application design.

Can the outputs use an external 24 V supply?

Yes. The bussed output supports internal or external field excitation. With an external source, the outputs can be galvanically isolated from the Series C power system.

What load information is needed before ordering?

Provide load voltage, steady and inrush current, number of simultaneously energized channels, field-power source, IOTA part number, redundancy requirement and the configured safe-state behavior.